Notice
Please ensure that this instruction manual is given to the final user of the instrument.
Preface
This instruction manual is meant for those who will be involved in the wiring, installation, operation and routine
maintenance of the SR90 series (SR91, SR92, SR93 and SR94) and describes matters to be attended to in handling
the SR90 series, how to install it, its wiring, its functions and operating procedures.
Keep this manual at the work site while handling the instrument and follow the guidance provided herein.
SR90F-1ME
Aug. 2019
SR90 Series
(SR91, SR92, SR93, SR94)
Digital Controller
Instruction Manual
Please check that the delivered product is the correct item or specification you ordered.
Please do not begin operating this product before you read this instruction manual
thoroughly and understand its contents.

Table of Contents

Questions and Answers

  • A
    Alexandra ColemanAug 19, 2025
    What to do if the Shimaden SR90 displays an incorrect PV value?
    • A
      Ashley CurryAug 20, 2025
      If the displayed PV value seems incorrect, verify that the set measuring range code is correct for the input signal. Also, check the wiring to the input terminals of the sensor and correct if necessary.
  • A
    Aaron FitzgeraldAug 21, 2025
    What to do if the Shimaden SR90 front panel display goes out and it stops operating?
    • K
      Kayla MartinezAug 21, 2025
      If the display on the front panel goes out and the instrument does not operate, inspect the power source and wiring connections, checking the wiring. Additionally, examine the product for deterioration and repair or replace it as needed.
  • A
    Anthony StanleyAug 23, 2025
    Why is my Shimaden SR90 Controller key unable to be operated?
    • A
      armstrongbiancaAug 25, 2025
      If a key is unable to be operated, it may be because the keylock is active, so release the keylock. Another reason could be deterioration of the product, in which case you should examine, repair, or replace the product. If the communication function is added, check if the communication mode (Com) has been set, and if so, change the communication setting to the local mode (Loc).
  • B
    Brian WeaverAug 26, 2025
    What to do if Shimaden SR90 Controller indicates higher limit side scaleover?
    • D
      Debra CollinsAug 26, 2025
      If the controller indicates a higher limit side scaleover, check the thermocouple input wiring for breaks and replace if necessary. Also, check R.T.D. input A wiring for breaks and replace the R.T.D. if needed. For voltage or current input, verify the transmitting unit of measured values and ensure the set code of the measuring range is correct for the input signal; it may be that the input measured value exceeded higher limit of measuring range by 10%.
  • L
    Lisa LeeAug 27, 2025
    How to fix too fast ON-OFF action of Shimaden SR90 Controller control output?
    • R
      rtorresAug 27, 2025
      If the ON-OFF action of the control output is too fast, increase the hysteresis value of the ON-OFF action.
  • P
    pbooneAug 29, 2025
    What does it mean if the Shimaden SR90 Controller shows a lower limit side scaleover?
    • B
      Benjamin MccarthyAug 29, 2025
      If the controller shows a lower limit side scaleover, check the wiring for reverse polarity or breaks in the measured value input; it may be that the input measured value fell from lower limit of measuring range by 10%.
  • G
    gonzalezanaAug 31, 2025
    What to do if Shimaden SR90 Controller displays higher limit side scaleover of cold junction (CJ)?
    • S
      ssimmonsAug 31, 2025
      If the controller displays a higher limit side scaleover of the cold junction (CJ), reduce the ambient temperature to the level provided in the environment conditions for the product, if the ambient temperature of the product has exceeded 80°C. In case ambient temperature has not exceeded 80°C, examine the product.
  • N
    Nicole WheelerSep 2, 2025
    What to do if Shimaden SR90 Controller displays higher limit side scaleover of cold junction (CJ) of thermocouple input?
    • L
      Leroy TuckerSep 2, 2025
      If the Shimaden Controller displays a higher limit side scaleover of the cold junction (CJ) of thermocouple input, raise the ambient temperature to the level provided in the environment conditions for the product if the ambient temperature of the product has fallen to -20°C or lower. In case ambient temperature has not fallen to í20°C or lower, examine the product.
  • A
    allisonsantanaSep 4, 2025
    What to do if there is a break of R.T.D. input wiring in Shimaden SR90 Controller?
    • T
      tracyheathSep 4, 2025
      Check R.T.D. input terminals A, B and B for breaks. If wiring has no problem, replace R.T.D.
  • P
    Peter HarperSep 6, 2025
    What does it mean if Shimaden SR90 Controller input value from heater current detector has exceeded 55.0A?
    • M
      Manuel BrownSep 6, 2025
      If the input value from the heater current detector has exceeded 55.0A, it indicates excess current. Reduce the current. Also, examine the product.

Summary

Safety Rules

Installation and Wiring

Wiring

Detailed wiring instructions, precautions, and diagrams for connecting the SR90 series controller.

Before Starting Operation

Step-by-step guide for initial setup and parameter configuration before operating the controller.

Explanation of Screens and Setting

Parameter Flow

Visual representation of the screen sequence and parameter flow for setting up the controller.

Procedure of Setting in Screen Group 0

Step-by-step guide for setting parameters within Screen Group 0.

Explanation of Screen Group and Setting

Explanation of Functions

Events

Explanation of different event types, including deviation and absolute value alarms.

Maintenance and Troubleshooting

Cause of Trouble and Troubleshooting

Table listing common problems, their causes, and recommended remedies.

Error Codes, Causes and Remedies

Detailed information on error codes, their causes, and specific remedies for measured value and alarm problems.

Specifications

Shimaden SR90 Series Specifications

General IconGeneral
BrandShimaden
ModelSR90 Series
CategoryController
LanguageEnglish