32
Ŷ Control output
Contact (Y): Contact (1a), 240V AC, 2.5 A: Resistive load/1 A: Inductive load
SSR drive voltage (P): 12 V ± 1.5 V DC (max. load current 20 mA)
Current (I): 4–20 mA, max. load resistance 600ȍ
Voltage (V): 0–10 V, max. current 2 mA
Output resolution: 10000 digits
Ŷ Event output (EV)
No. of output: Standard 2 points (EV1–EV2)
Constant rating: Contact (1a), 240 V AC, 1 A: Resistive load (common)
Function: Display: Action
Hd: Higher limit deviation value action
Ld: Lower limit deviation value action
od: Outside higher/lower limit deviation action
id: Inside higher/lower limit deviation action
HA: Higher limit absolute value action
LA: Lower limit absolute value action
SO: Scaleover
RUN: Control execution
ROT1: Control output inverted output (contact output only)
STPS: Step signal
PTNS: Pattern signal
ENDS: Program end signal
HOLD: Hold signal
PROG: Program signal
U_SL: Upslope signal
D_SL: Downslope signal
GUA: Guarantee soak
Ɣ Setting range
Absolute value: Within both measuring range and PV limiter (both higher and lower limit)
Deviation: -1999–2000 digits (both higher and lower limit)
Higher/lower deviation: 0–2000 digits (both inside and outside)
Action: ON-OFF action
Hysteresis: 1–999 digits
Action delay time: OFF, 1–9999 sec.
Standby action: Separate setting (separate output), selectable from any of 4 types below
1) Without
2) Standby 1 (when starting power, when RST ON ĺ OFF)
3) Standby 2 (when starting power, when RST ON ĺ OFF, when execution SV is changed)
4) Standby 3 (Does not output when there is input abnormality.)
Latching: Selection from Yes/No
Output characteristics: Selection from NO/NC
Output update cycle: 500 ms
Isolation: Insulated from all input and output (uninsulated within EV)
Ŷ External control input (DI)
No. of input: Standard 1 point
Input type: Level input, edge input
Input rating: Voltage 5 V DC (2.5 mA/1 input)
Input action: Non-voltage contact or open collector
Input holding time: 500 ms
Function: Display: Action: Input type
RUN1: Starts control when ON: Level
RUN2: Starts control when ON: Edge
MAN: Manual control output mode: Level
AT: AT execution: Edge
SV: SV switch: Level
RAMP: Ramp halt: Level
ACT: Output characteristics: Level
L_RS: Event latching release: Edge
PROG: Program switch: Level
HLD: Hold signal: Level
ADV: Advance signal: Edge
Ŷ Program (option)
No. of pattern: 1
No. of step: 10
Power failure
compensation: Without
Guarantee soak zone:
oFF, 1–999 digits
Time accuracy: Set value × 0.3%