19
External reset input function
By connecting External reset input terminals 9 and 12 (while the RESET indicator is lit), the RESET
indicator goes off, OUT1 (Limit control output terminals 15 and 16) is turned ON, and limit control
action initiates.
However, while the EXCEEDED indicator is lit, limit control action does not initiate even though
External reset input terminals 9 and 12 are shorted.
Contact 9-12 Open: Reset OFF
Contact 9-12 Closed: Reset ON
Circuit current when closed: 16 mA
Circuit insulation configuration
Insulation resistance: 10 M or more, at 500 V DC
Dielectric strength: Between input terminal and power terminal: 1.5 kV AC for 1 minute
Between output terminal and power terminal: 1.5 kV AC for 1 minute
Supply voltage: 100 to 240 V AC 50/60 Hz, 24 V AC/DC 50/60 Hz
Allowable voltage fluctuation: 100 to 240 V AC: 85 to 264 V AC
24 V AC/DC: 20 to 28 V AC/DC
Power consumption:
100 to 240 V AC: Approx. 8 VA max.
(When the maximum number of options are ordered: Approx. 11 VA max.)
24 V AC: Approx. 5 VA max. (When the maximum number of options are ordered: Approx. 8 VA max.)
24 V DC: Approx. 5 W max. (When the maximum number of options are ordered: Approx. 8 W max.)
Ambient temperature: -10 to 55 (14 to 131 ) (Non-condensing, No icing)
Ambient humidity: 35 to 85 %RH (Non-condensing)
Weight: Approx. 220 g
External dimensions: 96 x 96 x 68 mm (W x H x D) (Depth of control panel interior: 60 mm)
Material: Flame-resistant resin (Case)
Color: Black (Case)