INSTRUCTION MANUAL
Micro-computer based digital indicating controller JCS-33A
JCS31JE1 2007.09
To prevent accidents arising from the misuse of this controller, please ensure the operator receives this manual.
SAFETY PRECAUTIONS
To ensure safe and correct use, thoroughly read and understand this manual before using this instrument.
This instrument is intended to be used for industrial machinery, machine tools and measuring equipment. Verify correct
usage after consulting purpose of use with our agency or main office. (Never use this instrument for medical purposes
with which human lives are involved.)
External protection devices such as protection equipment against excessive temperature rise, etc. must be installed, as
malfunction of this product could result in serious damage to the system or injury to personnel. Also proper periodic
maintenance is required.
This instrument must be used under the conditions and environment described in this manual. Shinko Technos Co., Ltd.
does not accept liability for any injury, loss of life or damage occurring due to the instrument being used under
conditions not otherwise stated in this manual.
Caution with respect to Export Trade Control Ordinance
To avoid this instrument from being used as a component in, or as being utilized in the manufacture of weapons of
mass destruction (i.e. military applications, military equipment, etc.), please investigate the end users and the final use
of this instrument. In the case of resale, ensure that this instrument is not illegally exported.
Warning
To prevent an electric shock or fire, only Shinko or other qualified service personnel may handle the inner assembly.
To prevent an electric shock, fire or damage to the instrument, parts replacement may only be undertaken by
Shinko or other qualified service personnel.
Caution
This instrument should be used according to the specifications described in the manual.
If it is not used according to the specifications, it may malfunction or cause a fire.
Be sure to follow the warnings, cautions and notices. Not doing so could cause serious injury or malfunction.
Specifications of the JCS-33A and the contents of this instruction manual are subject to change without notice.
This instrument is designed to be installed through a control panel. If it is not, measures must be taken to ensure
that the operator cannot touch power terminals or other high voltage sections.
Be sure to turn the power supply to the instrument OFF before cleaning this instrument.
Use a soft, dry cloth when cleaning the instrument. (Alcohol based substances may tarnish or deface the unit.)
As the display section is vulnerable, do not strike or scratch it with a hard object.
Any unauthorized transfer or copying of this document, in part or in whole, is prohibited.
Shinko Technos CO., LTD. is not liable for any damage or secondary damage(s) incurred as a result of using
this product, including any indirect damage.
1. Model
1.1 Model
J C S 3 3 ,
Series name: JCS-33A (W48 x H48 x D95mm)
Control action
3
PID
A1
A
Alarm type can be selected by keypad. *1
Control output
(OUT1)
R
Relay contact: 1a
S
Non-contact voltage (for SSR drive): 12
+2
0
V DC
A
DC current: 4 to 20mA DC
Input
M
Multi-range *2
Supply voltage
100 to 240V AC (standard)
1
24V AC/DC *3
Option
A2
Alarm 2 (A2) *1
W (5A)
Heater burnout alarm
CT rated current: 5A
W (10A)
CT rated current: 10A
W (20A)
CT rated current: 20A
W (50A)
CT rated current: 50A
DT
Heating/Cooling control,
Control output (OUT2)
Non-contact relay
C5
Serial communication (RS-485)
SM
SV1/SV2 external selection
LA
Loop break alarm
BK
Color Black
TC
Terminal cover
*1: Alarm types (9 types and No alarm action) and Energized/Deenergized can be selected by keypad.
*2: Thermocouple, RTD, DC current, and DC voltage can be selected by keypad.
*3: Supply voltage 100 to 240V AC is standard. When ordering 24V AC/DC, enter 1 after the input code.
和文は裏面をご覧下さい

Questions and Answers

  • C
    curtismirandaJul 27, 2025
    Why is the PV display indication abnormal on my Shinko Controller?
    • M
      Mary HernandezJul 27, 2025
      An abnormal or unstable PV display indication on your Shinko Controller could be due to several reasons. Ensure the sensor input or temperature unit is correctly selected and that the sensor correcting value is suitable. Verify the sensor specification is correct. AC leakage into the sensor circuit can also cause this issue; try using an ungrounded type sensor. Additionally, nearby equipment may be causing interference; keep such equipment away from the controller.
  • R
    robertduncanAug 1, 2025
    What to do if the temperature does not rise with Shinko Controller?
    • S
      smannAug 1, 2025
      If the temperature isn't rising, the sensor may be faulty and needs replacement. Check that the sensor and control output terminals are securely connected to the instrument input terminals, and verify that the wiring of these terminals is correct.
  • M
    Mrs. Krista GarciaAug 5, 2025
    Why is my Shinko JCS-33A PV display flashing?
    • K
      Kelly KellyAug 5, 2025
      A flashing display on your Shinko Controller could indicate a burnt-out thermocouple, RTD, or DC voltage (0 to 1V DC). To check the sensor: * For Thermocouples: Short the input terminals; if a value around room temperature is indicated, the sensor may be burnt out. * For RTDs: Connect approximately 100 of resistance to the input terminals between A-B, and short between B-B; if approximately 0 (32 ) is indicated, the sensor may be burnt out. * For DC voltage (0 to 1V DC): Short the input terminals; if a scaling low limit value is indicated, the signal wire may be disconnected. Also, ensure the input terminals of the sensor are securely mounted to the instrument input terminals.
  • K
    Katelyn SullivanAug 9, 2025
    How to fix blank PV display on Shinko JCS-33A Controller?
    • T
      Tiffany SotoAug 9, 2025
      If the PV display is blank, the control output OFF function may be active. Press the key for approximately one second to release this function.
  • J
    jessica83Aug 13, 2025
    What to do if Shinko JCS-33A Controller PV display indicates Scaling low limit value?
    • E
      Edward BrooksAug 13, 2025
      If the PV display continuously shows the value set during Scaling low limit setting, check if the input signal source for DC voltage (0 to 5V DC, 0 to 10V DC) or DC current (0 to 20mA DC) is disconnected. For DC voltage, if the input to the terminals is 0V DC and the scaling low limit value is indicated, the signal wire may be disconnected. For DC current, if the input is 0mA DC and the scaling low limit value is indicated, the signal wire may be disconnected. Also, verify that the input lead wire terminals for DC voltage or DC current are securely mounted to the instrument input terminals.
  • M
    Michael PhillipsAug 18, 2025
    Why is the control output always OFF on my Shinko JCS-33A?
    • C
      cohenrebeccaAug 18, 2025
      If the control output remains in an OFF status, the OUT1 or OUT2 high limit value may be set to 0% or less in Auxiliary function setting mode 2. Set it to a suitable value.
  • P
    powerswilliamAug 22, 2025
    Why is the control output always ON on my Shinko JCS-33A?
    • V
      Valerie MillerAug 22, 2025
      If the control output remains in an ON status, the OUT1 or OUT2 low limit value may be set to 100% or higher in Auxiliary function setting mode 2. Set it to a suitable value.

Summary

Safety Precautions

Warning

General warnings about electrical shock and handling.

Caution

Cautions regarding usage, fire hazards, and handling.

Mounting to the control panel

Site selection

Guidelines for choosing a suitable location for installation.

Mounting

Instructions and cautions for physically mounting the controller.

Wiring

Operation

Main setting mode

Describes the parameters and settings available in the main mode.

Operation Steps

Auto-tuning of this controller

Troubleshooting

Indication Issues

Solves issues related to the controller's display indications.

Key Operation Issues

Solves problems related to using the controller's keys and buttons.

Control Issues

Provides solutions for control-related problems like temperature not rising.

Shinko JCS-33A Specifications