Manually set the desired distance for “4 mA”
Operating example or steps:
RUN mode
→ Q
1
Output
/ to → Q
2
Output
→ Function Q
2
/Q
a
/ to → Manual Q
a
→ 00200 (Note: 0 = flashing 0)
/ , / , / , / ,
/ → desired distance in mm
→ Saved
to → RUN mode
Necessary default settings:
Factory setting or function Q
2
/Q
a
=
4-20 mA
Mode Q
a
= Distance (only for user
level = Advanced)
Factory setting:
200 mm
Manually set the desired distance for “20 mA”
Operating example or steps:
RUN mode
→ Q
1
Output
/ to → Q
2
Output
→ Function Q
2
/Q
a
/ to → Manual Q
a
→ 4 mA
/ to → 20 mA
→ 30000 (Note: 3 = flashing 3)
/ , / , / , / ,
/ → desired distance in mm
→ Saved
to → RUN mode
Necessary default settings:
Factory setting or function Q
2
/Q
a
=
4-20 mA
Mode Q
a
= Distance (only for user
level = Advanced)
Factory setting:
30,000 mm
Activate the “0-10 V” output function or analog voltage output
Operating example or steps:
RUN mode
→ Q
1
Output
/ to → Q
2
Output
→ Function Q
2
/Q
a
→ 4-20 mA
/ to → 0-10 V
→ Saved
to → RUN mode
Necessary default settings:
-
Factory setting:
4-20 mA
OPERATION 6
8017154/1AVV/2021-03-24 | SICK O P E R A T I N G I N S T R U C T I O N S | DT50-2 Pro
53