76 Operating Instructions | SICK
Operating Instructions PAC50
8017612/ZAB1/2017-02-14 | PAC50
Subject to change without notice
8 Errors
8.3: Analogue output behavior in the event of an error
p
p
UL
OL
4,0
3,8
20,0
I / mA
Lower limit of measuring range
4,0
3,8
20,0
I / mA
Analog output
4 mA … 20 mA
(normal function)
Analog output
4 mA … 20 mA
(inverted mode)
20 mA … 4 mA
Upper limit of measuring range
20,5
20,5
Figure 15: Analogue output behavior in the event of an error (1)
Valid range of current output according to NAMUR NE43: Max. current output 20.5 mA / Min. current output 3.8 mA.
There might be a discontinuity between the linear range MBA…MBE...OL and the range between MBE and OL. The same for UL...MBA.