Table 9: Fault indicators
STATUS light
emitting
diodes (green)
DIAG light
emitting
diodes (red)
Possible cause OSSD state
o o
No supply voltage OFF
Ö Flashes
three times
Ö Flashes
three times
Start sequence with self-test OFF
O o
Protective device closed and lock activated ON
o O
Locking command inactive OFF
Ö 4Hz o
Locking command active, but the actuator is
not in scanning range or the actuator is invalid
in the scanning range.
OFF
Ö 1Hz o
Protective device closed and lock activated,
output signal switching device signal at inputs
In1 and In2 invalid or not present
OFF
Ö Flashes
three times
Ö Flashes
once
Lock cannot be activated or deactivated
because actuator is not aligned correctly
OFF
o Ö 1Hz
Fault at output signal switching devices. When
fault is eliminated, perform reset by interrupt‐
ing the voltage supply.
OFF
o Ö 4Hz
Fault when activating or deactivating lock.
Align actuator correctly and perform reset
by interrupting the voltage supply.
General fault. Perform reset by interrupting
the voltage supply. If the reset does not
rectify the fault, replace the device.
Actuator was moved outside sensing range
during locked state. Check the alignment of
the door.
Interference from similar device nearby
(≤200mm). Increase the distance and
reset the device.
Actuator damaged. Replace the actuator.
OFF
TROUBLESHOOTING 8