Table 9: Fault indicators
STATUS light
emitting
diodes (green)
DIAG light
emitting
diodes (red)
Possible cause OSSD state
o o
No supply voltage OFF
Ö Flashes
three times
Ö Flashes
three times
Start sequence with self-test OFF
O o
Protective device closed and lock activated ON
o O
Locking command inactive OFF
Ö 4Hz o
Locking command active, but the actuator is
not in scanning range or the actuator is invalid
in the scanning range.
OFF
Ö 1Hz o
Protective device closed and lock activated,
output signal switching device signal at inputs
In1 and In2 invalid or not present
OFF
Ö Flashes
three times
Ö Flashes
once
Lock cannot be activated or deactivated
because actuator is not aligned correctly
OFF
o Ö 1Hz
Fault at output signal switching devices. When
fault is eliminated, perform reset by interrupt‐
ing the voltage supply.
OFF
o Ö 4Hz
■
Fault when activating or deactivating lock.
Align actuator correctly and perform reset
by interrupting the voltage supply.
■
General fault. Perform reset by interrupting
the voltage supply. If the reset does not
rectify the fault, replace the device.
■
Actuator was moved outside sensing range
during locked state. Check the alignment of
the door.
■
Interference from similar device nearby
(≤200mm). Increase the distance and
reset the device.
■
Actuator damaged. Replace the actuator.
OFF
TROUBLESHOOTING 8