Maintenance and service
7.10 Updating the IM 153-x
ET 200M
Operating Instructions, 04/2022, EWA-4NEB7806006-09
117
Principle
An update is possible with IM 153-2 as of order number 6ES7153-2Bx00-0XB0. You will
require STEP 7 (V5.2 or higher) for this purpose.
There are 3 ways in which you can perform an update:
from PD / PC via PROFIBUS DP (direct)
from PD / PC via PROFIBUS DP and CPU
via SIMATIC Micro Memory Card
After a successful update the former firmware version of the IM 153-2 must be covered over
with a sticker showing the updated version of the firmware.
Requirements
For update via PROFIBUS-DP
The IM 153-2 in the station that is to be updated must be available online.
The files with the current (new) version of the firmware must be available in the file
system of your PD / PC.
for update via SIMATIC Micro Memory Card
The update files must be available on the SIMATIC Micro Memory Card.
Example configuration
Update from PD / PC via PROFIBUS DP (direct)
The PG / PC with the update files is directly connected to the PROFIBUS interface of the IM
153-2 (refer to the following figure).
Note
If no STEP
7 project containing the respective IM 153-2 is available, then the update can also
take place via the online view (available nodes) in STEP 7.