10.2 Parameters of the IM 153-x
ET 200M
228 Operating Instructions, 04/2022, EWA-4NEB7806006-09
Laser protection class approval (for IM 153-2 FO)
Class 1 according to EN 60825-1: 1994+A11: 1996 or IEC 60825-1: 1993 including
Amendment 1:1997
The radiation powers accessible when the fiber-optic cable is opened intentionally /
unintentionally correspond to hazard level 1 according to EN 60825-2: 1994 or
IEC 60825-2: 1993.
10.2 Parameters of the IM 153-x
Parameter assignment
You configure the IM 153-x or the ET 200M with STEP 7 or COM PROFIBUS. If you use a
different configuration tool, you must integrate the GSD file.
Table 10- 2 Parameters of the IM 153 x
Parameters
Range of values
Default
Scope
DPV1 mode
block / enable
enable
ET 200M
Start up at preset actual con-
figuration?
yes/no
No
ET 200M
"Module change during opera-
tion"?
yes/no
No
ET 200M
Diagnostic Interrupt
block / enable
enable
ET 200M
Process interrupt
block / enable
enable
ET 200M
Removing / insertion interrupt
block / enable
enable
ET 200M
Analog-value format
SIMATIC S7 / SIMATIC S5
SIMATIC S7
ET 200M
Enhanced diagnostics
yes/no
No
ET 200M
No: 29 bytes;
Yes: 64 bytes with IM 153-1 or
96 bytes with IM 153-2 diagnostic
frame
Module diagnostics
block / enable
enable
ET 200M
Module status
block / enable
enable
ET 200M
Channel-specific diagnostics
block / enable
enable
ET 200M