Connecting
5.4 Wiring the power supply and modules
ET 200M
78 Operating Instructions, 04/2022, EWA-4NEB7806006-09
5.4 Wiring the power supply and modules
5.4.1 Wiring rules
Note
For a configuration for "Module change during operation", provide
longer cables to the front
connectors (refer to chapter "Wiring front connectors of the signal modules (Page 81)").
Table 5- 1 Wiring rules for the power supply and the IM 153-x
Wiring rules for ...
Power supply and IM 153-x
connectable wire cross-sections for solid cables
No
connectable wire cross-sections for
flexible cables
without wire end ferrules
0.25 to 2.5 mm
2
with wire end ferrules
0.25 to 1.5 mm
2
Number of wires per connection
1 or combination of 2 wires up to 1.5 mm
2
(total)
in a mutual wire end ferrule
Maximum external diameter of the wire insulation
Ø 3.8 mm
Stripping length of the wires
without insulation collar
11 mm
with insulation collar
11 mm
Wire end ferrules in accordance with
DIN 46228
without insulation collar
Form A, 10 to 12 mm long
with insulation collar
Form E, up to 12 mm long
Table 5- 2 Wiring rules for front connectors of modules
Wiring rules for ... Front connectors of modules
(screw and spring terminals)
20-pin
40-pin
connectable wire cross-sections for solid wires
No
No
connectable wire cross-
sections for flexible wires
without end sleeve
0.25 to 1.5 mm
2
0.14 to 0.75 mm
2
with wire end ferrules
0.25 to 1.5 mm
2
0.14 to 0.75 mm
2
Number of wires per connection
1 or a combination of 2 wires
up to 1.5 mm
2
(total) in a
common wire end sleeve
1 or combination of 2 wires
up to 0.75 mm
2
(total) in a
mutual wire end ferrule
Maximum external diameter of the wire insulation
Ø 3.1 mm
max. 20 cables
Ø 2.0 mm
max. 40 cables
Stripping length of the wires
without insulation collar
6 mm
6 mm
with insulation collar
6 mm
6 mm
End sleeves in accordance
with DIN 46228
without insulation collar
Form A, 5 to 7 mm long
Form A, 5 to 7 mm long
with insulation collar
Form E, up to 6 mm long
Form E, up to 6 mm long