Siemens 6ES7153-2BA10-0XB0 - Structure of the Process Interrupt

Siemens 6ES7153-2BA10-0XB0
271 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
8.2 Time stamping the input signals with IM 153-2
ET 200M
Operating Instructions, 04/2022, EWA-4NEB7806006-09
151
Parameterizing the edges
Time stamp with edge 0 1:
With a signal change on the digital input of 0 1 a signal message with signal status 80h
(incoming) is stored in the data record (DS 100 to 114).
Time stamp with edge 1 0:
With a signal change on the digital input of 1 0 a signal message with signal status 80h
(incoming) is stored in the data record (DS 100 to 114).
Example
For a fully connected ET 200M (8 digital inputs with in each case 16 digital inputs) the data
record 240 has a total of 50 bytes for the configuration of the time stamp.
Return values on DS_WRITE
Possible return values on writing a data record can be obtained in accordance with the DPV1
standard.
8.2.4.6 Structure of the process interrupt
Structure of the alarm information
The process interrupt is structured in accordance with the DPV1 standard.
Table 8- 1 Contents of the diagnostic frame (example)
Value
Meaning
00 0C 00h
Station status
05h
Master address (e.g. B 5)
80 1Eh
Manufacturer ID
43 00 00h
Module diagnostics (variable length, here 3 bytes)
07 82 00 00 00 00 00h
Module status (variable length, here 7 bytes)
08 02 02 20 00 67 01 0Dh
Interrupt part with time stamping