Technical Specifications
10.1 Standards and approvals
ET 200M
224 Operating Instructions, 04/2022, EWA-4NEB7806006-09
ATEX approval
According to EN 60079-15 (Electrical apparatus for potentially explosive atmospheres - Part
15: Type of protection "n") and EN 60079-0 (Electrical apparatus for potentially explosive
atmospheres - Part 0: General Requirements) and EN 60079-0 (Electrical apparatus for
potentially explosive atmospheres - Part 0: General requirements).
II 3 G Ex nA IIC Tx Gc
DEKRA 13ATEX0015 X
OR
According to EN IEC 60079-7 (Electrical apparatus for potentially explosive atmospheres - Part
7: Increased safety "e") and EN 60079-0 (Electrical apparatus for potentially explosive
atmospheres - Part 0: General Requirements), EN 60079-15 (Electrical apparatus for
potentially explosive atmospheres Part 15: Type of protection "n") and EN IEC 60079-0
(Electrical apparatus for potentially explosive atmospheres - Part 0: General requirements).
II 3 G Ex ec nC IIC Tx Gc
DEKRA 21ATEX0048 X
Special conditions in explosive atmospheres:
The equipment shall only be used in an area of not more than pollution degree 2, as
defined in EN 60664-1.
The equipment shall be installed in a suitable enclosure providing a degree of protection
not less than IP54 in accordance with EN IEC 60079-0. The ambient conditions must be
taken into consideration for use.
Provisions shall be made to prevent the rated voltage from being exceeded by transient
disturbances of more than 119 V.
UKEX approval
According to EN IEC 60079-7 (Explosive atmospheres Part 7: Equipment protection by
increased safety "e"), EN 60079-15 (Electrical apparatus for potentially explosive atmospheres
- Part 15: Equipment protection by type of protection "n") and EN IEC 60079-0 (Explosive
atmospheres Part 0: Equipment - General requirements).
II 3 G Ex ec nC IIC Tx Gc
DEKRA 21UKEX0011 X
Special conditions in explosive atmospheres:
The equipment shall only be used in an area of not more than pollution degree 2, as
defined in EN 60664-1.
The equipment shall be installed in a suitable enclosure providing a degree of protection
not less than IP54 in accordance with EN IEC 60079-0. The ambient conditions must be
taken into consideration for use.
Provisions shall be made to prevent the rated voltage from being exceeded by transient
disturbances of more than 119 V.