EasyManua.ls Logo

Siemens 6ES7153-2BA70-0XB0 - Time Stamping Outside of S7-400; Prerequisites

Siemens 6ES7153-2BA70-0XB0
271 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
8.2 Time stamping the input signals with IM 153-2
ET 200M
Operating Instructions, 04/2022, EWA-4NEB7806006-09
141
8.2.4 Time stamping outside of S7-400
8.2.4.1 Prerequisites
With the interface module IM 153-2Bxx1, time stamping is also possible outside of an S7-400
automation system.
The above principles and rules apply - if complied with, precisions of up to 1 ms can be
achieved.
Synchronization interval for the time: 10 s
Demands on the ET 200M and DP master
ET 200M:
IM 153-2 as of order number 6ES7153-2Bxx1-0XB0
suitable DI modules
IM 153-2 must be configured via GSD rev. 5 (e.g. enabling of interrupts)
for IM 153-2 the DPV1 mode must be activated
Synchronization interval in accordance with the setting on the clock master
DP master:
must fulfill requirements in accordance with DPV1
must be able to process interrupts
must be able to process data records (read / write)
must be able to send / forward time message frames or a clock master must be available in
the same PROFIBUS DP line

Table of Contents

Related product manuals