Installation
4.3 Setting the PROFIBUS address
ET 200M
68 Operating Instructions, 04/2022, EWA-4NEB7806006-09
Attaching slot numbers
The following figure shows how you must attach the slot numbers. The slot number plates
are provided with the IM 153-x.
Figure 4-3 Attach the slot numbers to the modules.
4.3 Setting the PROFIBUS address
Definition
Each bus node must receive a PROFIBUS address to identify it uniquely on the PROFIBUS DP.
Controlling
The following rules apply for the PROFIBUS address of the IM 153-x:
• Permissible PROFIBUS addresses are: 1 to 125.
• Each PROFIBUS address can be allocated only once on the bus.