Installation
4.3 Setting the PROFIBUS address
ET 200M
Operating Instructions, 04/2022, EWA-4NEB7806006-09
69
Setting the PROFIBUS Address
1. Set the PROFIBUS address using a screwdriver and with the door open.
The PROFIBUS address is the addition of the switch that is located on the right ("ON"
position).
-2Bx00 and the IM 153-2Bxx1 the PROFIBUS address has an 8-pin DIL switch
-pin switch that has been used up until now.
The lowest switch has no function and is labeled with "0" or "
-" in order to maintain the
Example: Setting the PROFIBUS Address
64 + 32 + 2 + 1 = 99
64 + 32 + 2 + 1 = 99
Switch 0 has no function.
64 + 32 + 2 + 1 = 99
The switch "-" has no function.
Changing the PROFIBUS Address
You can change the set PROFIBUS address at any time. However, the IM 153-x adopts the
new PROFIBUS address only after a switch off / switch on of the 24 V DC supply.