Interrupt, error and system messages
9.1 PROFIBUS DP
ET 200M
182 Operating Instructions, 04/2022, EWA-4NEB7806006-09
LEDs
Meaning Remedy
SF
BF
ON
on
off
on
inadmissible PROFIBUS address
Is the SF LED of an SM / FM also lit?
If so: Error or diagnosis in an S7 300 mod-
ule
If not: IM 153-1 is faulty.
On the IM 153-1 set a valid PROFIBUS address (1 to
125)
Check the SM / FM with the diagnostics. Replace
the S7-300 module or the IM 153-1 or contact your
Siemens representative.
off
off
on
There is data exchange between the DP master
and the ET 200M.
The preset configuration and actual configura-
tion of the ET 200M match.
* not relevant
Status and error displays of the IM 153-2
Table 9- 2
LEDs
Meaning Remedy
SF BF /
BF1
ACT ON
off
off
off
off
No voltage on the IM 153-2 or there is a
hardware fault with the IM 153-2.
Switch on the power supply module or
replace the IM 153-2.
*
*
*
on
There is voltage on the IM 153-2. IM 153-2
is functioning.
on
off
off
off
IM 153-2 is undergoing a hardware reset
after switching on
on
on
on
on
Hardware test after switching on
on
on
off
off
The operating system update is running
off
flashes
at
0.5 Hz
off
off
The operating system update has conclud-
ed successfully
with IM 153-2Bx00:
remove the SIMATIC Micro Memory card
and switch off the IM 153-2.
on
flashes
at
0.5 Hz
off
off
external error, e.g. unsuitable operating
system or SIMATIC Micro Memory card
Use a suitable operating system for the
update.
Do not remove the SIMATIC Micro Memory
card during the update (only with IM 153-
2Bx00).
on
flashes
at
2 Hz
off
off
internal error, e.g. when writing the up-
date files
Repeat the update process.
If the LEDs indicate an error, the internal
memory is faulty.