Interrupt, error and system messages
9.1 PROFIBUS DP
ET 200M
182 Operating Instructions, 04/2022, EWA-4NEB7806006-09
Meaning Remedy
inadmissible PROFIBUS address
Is the SF LED of an SM / FM also lit?
• If so: Error or diagnosis in an S7 300 mod-
ule
If not: IM 153-1 is faulty.
On the IM 153-1 set a valid PROFIBUS address (1 to
125)
Check the SM / FM with the diagnostics. Replace
the S7-300 module or the IM 153-1 or contact your
Siemens representative.
There is data exchange between the DP master
and the ET 200M.
The preset configuration and actual configura-
tion of the ET 200M match.
Status and error displays of the IM 153-2
Table 9- 2
Meaning Remedy
SF BF /
ACT ON
No voltage on the IM 153-2 or there is a
hardware fault with the IM 153-2.
Switch on the power supply module or
replace the IM 153-2.
There is voltage on the IM 153-2. IM 153-2
is functioning.
IM 153-2 is undergoing a hardware reset
after switching on
Hardware test after switching on
The operating system update is running
at
The operating system update has conclud-
ed successfully
remove the SIMATIC Micro Memory card
and switch off the IM 153-2.
at
0.5 Hz
external error, e.g. unsuitable operating
system or SIMATIC Micro Memory card
Use a suitable operating system for the
update.
Do not remove the SIMATIC Micro Memory
card during the update (only with IM 153-
at
2 Hz
internal error, e.g. when writing the up-
date files
Repeat the update process.
If the LEDs indicate an error, the internal