Technical Specifications
10.1 Standards and approvals
ET 200M
Operating Instructions, 04/2022, EWA-4NEB7806006-09
225
IECEx approval
According to IEC 60079-15 (Explosive atmospheres - Part 15: Equipment protection by type of
protection "n") and IEC 60079-0 (Explosive atmospheres - Part 0: Equipment - General
requirements).
II 3 G Ex ec IIC Tx Gc
DEKRA 21DEK 14.0042 X
OR
According to IEC 60079-7 (Electrical apparatus for potentially explosive atmospheres - Part 7:
Increased safety “e”), IEC 60079-15 (Electrical apparatus for potentially explosive
atmospheres - Part 15: Type of protection "n") and IEC 60079-0 (Electrical apparatus for
potentially explosive atmospheres - Part 0: General requirements).
II 3 G Ex ec nC IIC Tx Gc
DEKRA 21DEK 21.0030 X
Special conditions in hazardous areas:
The equipment shall only be used in an area of not more than pollution degree 2, as
defined in IEC 60664-1.
The device must be installed in a suitable housing that ensures at least IP54 degree of
protection according to IEC 60079-0. The ambient conditions must be taken into
consideration for use.
Provisions shall be made to prevent the nominal voltage from being exceeded by transient
interference voltage of more than 119 V.
CCCEx approval
According to GB/T 3836.3 (Explosive atmospheres - Part 3: Equipment protection by type of
protection "e") and GB/T 3836.8 (Explosive atmospheres - Part 8: Equipment protection by
type of protection "n") and GB/T 3836.1 (Explosive atmospheres - Part 1: Equipment -
General requirements).
Ex ec nC IIC Tx Gc
Special conditions in hazardous areas:
The equipment shal
l only be used in an area of not more than pollution degree 2, as
defined in GB/T 16935.1.
The equipment shall be installed in a suitable enclosure providing a degree of protection
not less than IP54 in accordance with GB/T 3836.1. The ambient conditions must be taken
i
nto consideration for use.
Provisions shall be made to prevent the nominal voltage from being exceeded by transient
disturbance voltages of more than 119 V.