Commissioning
6.1 PROFIBUS DP
ET 200M
88 Operating Instructions, 04/2022, EWA-4NEB7806006-09
Only for DP interface FOC:
If the DP slave is located at the end of an FOC line, then the unused FOC interface must be
closed with a dummy plug.
DP slave configured (refer to the online help / manual on configuration software)
Note
when configuring with GSD file
When using an IM
153-2BA81 (outdoor) you must convert the user parameter "MLFB" to
6ES7153
-2BA81-0XB0.
If you configure the ET
200M (IM 153-2BAx2) with a GSD file, the length of the parameter
assignment message frame (maximum 244
bytes) can lead to limitations in the numb
er of
assignable modules.
Supply voltage for DP master switched on (refer to the DP master manual)
Configuration loaded into the DP master (refer to the online help / manual on
configuration software)
DP master switched to RUN (refer to the DP master manual)
Commissioning the DP slave
Commission the DP slave as follows:
1. Switch on the supply voltage for the DP slave.
2. If necessary, switch on the supply voltage for the load.