Parameter reference
SITRANS LR250 with mA/HART
Operating Instructions, 10/2019, A5E32220602-AG
119
Material Level (2.5.1.)
Note
The default setting depends whether your device is a standard or NAMUR NE 43
-compliant
Defines the mA output to use when the Fail-safe timer expires.
Last valid reading (default 22.6 mA)
User-selected value [defined in Fail-Safe mA Value (2.5.3.)]
NAMUR NE 43-COMPLIANT DEVICE
1)
* VALUE User-selected value [defined in
Fail-Safe mA Value (2.5.3.)
: default
LOE Timer (2.5.2.)
Note
When a Loss of Echo occurs Material Level (2.5.1.)
determines the material level to be
-safe timer expires. See Loss of Echo (LOE) (Page 243)
for more
Sets the time to elapse since the last valid reading, before the Fail-safe Level is reported.
Range: 0.00 to 7200 seconds