Diagnosing and troubleshooting
10.4 Operation troubleshooting
SITRANS LR250 with mA/HART
172 Operating Instructions, 10/2019, A5E32220602-AG
10.4 Operation troubleshooting
Operating symptoms, probable causes, and resolutions.
Symptom
Cause
Action
Display shows
level or target is out of range
check specifications
check
Low Calibration Pt. (2.3.1.)
increase
Confidence (2.8.6.1.)
Display shows
material build-up on antenna
clean the antenna
re-locate SITRANS LR250
Display shows
location or aiming:
poor installation
flange not level
Auto False Echo Suppression
may be incorrectly applied
check to ensure nozzle is vertical
ensure end of antenna protrudes from end of nozzle
review Auto False Echo Suppression (Page 238
)
.
ensure Auto False Echo Suppression Range is set correct-
ly
Display shows
antenna malfunction:
temperature too high
physical damage
excessive foam
multiple echoes
check
Current Internal Temperature (3.2.1.)
use foam deflector or stillpipe
relocate
use a defoamer
set
Algorithm (2.8.4.1.)
to
F
(First echo)
Reading does not
change, but the level
does
SITRANS LR250 processing
wrong echo, for example, vessel
wall, or structural member
re-locate SITRANS LR250
check nozzle for internal burrs or welds
rotate device 90°
use
Auto False Echo Suppression (2.8.7.1.)
if necessary: see Auto False Echo Suppression
(Page 238).
Measurement is con-
sistently off by a con-
stant amount
setting for
Low Calibration Pt.
(2.3.1.)
not correct
setting for
Sensor Offset
(2.3.3.)
not correct
check distance from sensor reference point to
Low Cali-
bration Pt. (2.3.1.)
check
Sensor Offset (2.3.3.)
Screen blank power error
check nameplate rating against voltage supply
check power wiring or source
too much load resistance
change barrier type, or
remove something from the loop, or
increase supply voltage
reduce wire distance or use larger gage wire
Reading erratic echo confidence weak
refer to
Confidence (2.8.6.1.)
use
Auto False Echo Suppression (2.8.7.1.)
and
Auto
False Echo Suppression Range (2.8.7.2.)
use foam deflector or stillpipe