Commissioning
6.3 Application examples
SITRANS LR250 with mA/HART
66 Operating Instructions, 10/2019, A5E32220602-AG
Quick Start Wiz-
ard parameters
Continue with current
Level is reported as
Volume when a vessel
Transfers Quick Start
Defines vessel shape.
Maximum Volume (2.7.1.2.)
Vessel Dimension A (2.7.1.3.)
Vessel Dimension L (2.7.1.4.)
Fail-safe level set to High
Return to Measurement: press Mode to start normal operation.
6.3.3 Application with stillpipe
(Blanking) will be set at the factory. Check the process connection
tag for specific values.
Suitable pipe diameters are 40 mm (1.5") to 100 mm (4").
The pipe diameter must be matched with the antenna size. Use the largest antenna size
that will fit the stillpipe/bypass pipe. See
Dimensions (Page 183).
See Mounting on a Stillpipe or Bypass Pipe (Page 32) for installation guidelines.
This application is to obtain a level measurement and corresponding 4 to 20 mA output
proportional to the oil level in a fuel storage vessel.
● Low Calibration Pt. is 5 m (16.5 ft) from the sensor reference point.
● High Calibration Pt. is 0.5 m (1.65 ft) from the sensor reference point.
● The stillpipe inside diameter is 50 mm (1.96").
● The maximum rate of filling or emptying is about 0.1 m (4")/min.