Remote operation
7.1 Operating via SIMATIC PDM
SITRANS LR250 with mA/HART
84 Operating Instructions, 10/2019, A5E32220602-AG
To set Device/Sensor Maintenance schedules:
1. Open the menu Device Maintenance, and click on the Remaining Device/Sensor
Lifetime tab.
2. Modify desired values, and if desired, set reminders for either or both of Reminder 1
before Lifetime (Required)/Reminder 2 before Lifetime (Demanded).
3. Click Write.
4. Click Read, to see the effects of your modification.
5. Click Snooze to add a year to the Total Expected Device Life.
To set Service/Calibration schedules:
1. Open the menu Device Maintenance, and click on the Service/Calibration Schedule tab.
2. Modify desired values and if desired, set reminders for either or both of Reminder 1
before Lifetime (Required)/Reminder 2 before Lifetime (Demanded).
3. Click Write.
4. Click Read, to see the effects of your modification.
5. Click Service/Calibration Performed to reset the schedule.
7.1.6.8 Select analog output
Allows you to set the mA Output to report Level, Distance, Space, or Volume. See Current
Output Function (2.6.1.) for an illustration.