Remote operation
7.2 Operating via AMS Device Manager
SITRANS LR250 with mA/HART
Operating Instructions, 10/2019, A5E32220602-AG
93
Master reset
Note
Device Address (5.1.)
remains unchanged if the reset command is sent remotely (via AMS,
PDM, DTM, FC375) but is reset to 0 if the reset command is sent via HMI.
Navigate to Configure/Setup > Operation
In the General field click on Master Reset and accept the option Factory Defaults.
7.2.1.6 Pull-down menu access
Action menu items
A pull-down menu under Actions gives alternative access to several features.
Scan Device
• Open the menu Actions Scan Device.
Scan Device uploads parameters from the device (synchronizes parameters).
7.2.1.7 Device configuration
1. Navigate to Configure/Setup > Operation and click to open the dialog window.
2. In the General field, click on Master Reset and perform a reset to Factory Defaults.
3. Open the pull-down menu Actions – Scan Device to synchronize parameters (upload
parameters from the device to AMS).
4. Configure the device via the Quick Start wizard.