Parameter reference
SITRANS LR250 with mA/HART
132 Operating Instructions, 10/2019, A5E32220602-AG
TVT Setup (2.8.7.)
Note
Default settings in the parameter tables are indicated with an
asterisk (*) unless explicitly
stated.
Auto False Echo Suppression (2.8.7.1.)
Used together with Auto False Echo Suppression Range (2.8.7.2.) to screen out false
echoes in a vessel with known obstructions. A ’learned TVT’ (time varying threshold)
replaces the default TVT over a specified range. See
Auto False Echo Suppression
(Page 238
) for a more detailed explanation.
Note
Make sure material level is below all known obstructions when Auto False Echo
Suppression is used to learn the echo profile. (An empty or almost empty vessel is
recommended.)
Note the distance to material level when Auto False Echo learns the environment. Set
Auto False Echo Suppression Range to a shorter distance to avoid the material echo
being screened out.
Set Auto False Echo Suppression and Auto False Echo Suppression Range during
startup, if possible.
If the vessel contains an agitator it should be running.
Before adjusting these parameters, rotate the instrument for best signal (lower false-
echo
amplitude).