Parameter reference
SITRANS LR250 with mA/HART
Operating Instructions, 10/2019, A5E32220602-AG
155
Security (6.)
Note
Default settings in the parameter tables a
re indicated with an asterisk (*) unless explicitly
Remote Access (6.1.)
Access Control (6.1.1.)
Note
If access control is changed to limit remote access, it can
only be reset via the handheld
Enables/disables the read/write access to parameters via remote communications.
Read only No changes are permitted via remote com-
Restricted Sets the status to Read only, with the poten-
tial for another HART device to change this
parameter only, via remote communications.
Local Access (6.2.)
Write Protect (6.2.1.)
Note
This lock affects only the handheld programmer. A remote master can change configuration
if Access Control (6.1.1.)
is set to allow this.
Prevents any changes to parameters via the handheld programmer.
Unlock value [stored in PIN to Unlock (6.2.2.)]
● To turn Lock On, key in any value other than the Unlock Value stored in PIN to Unlock
(6.2.2.).
● To turn Lock Off, key in the Unlock Value stored in PIN to Unlock (6.2.2.).