Parameter reference
SITRANS LR250 with mA/HART
Operating Instructions, 10/2019, A5E32220602-AG
155
Security (6.)
Note
Default settings in the parameter tables a
re indicated with an asterisk (*) unless explicitly
stated.
Remote Access (6.1.)
Access Control (6.1.1.)
Note
If access control is changed to limit remote access, it can
only be reset via the handheld
programmer.
Enables/disables the read/write access to parameters via remote communications.
Options
Read only No changes are permitted via remote com-
munications.
*
Read Write
Changes are permitted.
Restricted Sets the status to Read only, with the poten-
tial for another HART device to change this
parameter only, via remote communications.
Local Access (6.2.)
Write Protect (6.2.1.)
Note
This lock affects only the handheld programmer. A remote master can change configuration
if Access Control (6.1.1.)
is set to allow this.
Prevents any changes to parameters via the handheld programmer.
Options
Range: 0 to 9999
*
Unlock value [stored in PIN to Unlock (6.2.2.)]
Lock Off
Any other value
Lock On
To turn Lock On, key in any value other than the Unlock Value stored in PIN to Unlock
(6.2.2.).
To turn Lock Off, key in the Unlock Value stored in PIN to Unlock (6.2.2.).