EasyManua.ls Logo

Siemens 7ML5431 - Page 31

Siemens 7ML5431
282 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installing/mounting
4.3 Proper mounting
SITRANS LR250 with mA/HART
Operating Instructions, 10/2019, A5E32220602-AG
31
Emission cone type and beam angle
Antenna type
Antenna size
Beam angle
Horn
1.5"
19°
2"
15°
3"
10°
4"
Threaded PVDF
19°
Process connection
size
Process connection type
PTFE flanged encapsulated
2"
Class 150 ASME B16.5
12.8°
3, 4, 6"
Class 150 ASME B16.5
9.6°
50A
10K JIS B 2220
12.8°
80A/100A/150A
10K JIS B 2220
9.6°
DN50
PN10/16 EN1092-1
12.8°
DN80/DN100/DN15
0
PN10/16 EN1092-1 9.6°
Hygienic encapsulated
2"
Sanitary Clamp according to
ISO 2852
12.8°
3, 4"
9.6°
DN50
Aseptic/Hygienic nozzle/slotted
nut according to DIN 11864-1
[Form A]
12.8°
DN80/DN100 9.6°
DN50
Aseptic/Hygienic flanged ac-
cording to DIN 11864-2 [Form
A]
12.8°
DN80/DN100 9.6°
DN50
Aseptic/Hygienic Clamp ac-
cording to DIN 11864-3 [Form
A]
12.8°
DN80/DN100 9.6°
DN50
Hygienic nozzle/slotted nut
according to DIN 11851
12.8°
DN80/DN100
9.6°
Type F (50 mm)
and Type N
(68 mm)
Tuchenhagen Varivent 12.8°
Emission cone
Keep emission cone free of interference from obstructions such as ladders, pipes, I-
beams, or filling streams.
Access for programming
Provide easy access for viewing the display and programming via the handheld
programmer.

Table of Contents