7SV512
Installation instructions
V1
49C53000---G1176---C91
If one tries toleave the setting range for the configu-
rationblocks (i.e. address blocks 60to 79) withkeys
Ý ß, the display shows the question ”END OF
CODEWORD OPERATION ?”. Press the ”No”---key
N to continue configuration. If you press the
”Yes”---key J/Y instead, another question appears:
”SAVE NEW SETTINGS ?”. Now you can confirm
with J/Y or abort with N, as above.
When one exits the setting program, the altered pa-
rameters, whichuntil then have beenstored inbuffer
stores, are permanently secured in EEPROMs and
protected against poweroutage. Ifconfiguration pa-
rameters have been changed the processor system
will reset andre-start. Duringrestart thedevice isnot
operational.
7 0 0 0 O P E R A T I N G
P A R A M E T E R S
Beginning of the block ”Operating parameters”
7 0 0 1 L A N G U A G E
D E U T S C H
E N G L I S H
Theavailable languages canbecalled up byrepeatedly
pressing the ”No”---key N. Each language is spelled in
the corresponding country’s language. If you don’t un-
derstand a language, you should find your own lan-
guage.
The required language is chosen with the enter key E.
7 0 0 2 O P E R . B A U D R .
1 2 0 0 B A U D
The transmission Baud-rate for communication via the
operating interface atthe front canbeadapted totheop-
erator’s communication interface, e.g. personal com-
puter,ifnecessary.The available possibilities canbedis-
played by repeatedly depression of the ”No”---key N.
Confirm the desired Baud-rate with the entry key E.
Note: For operator panel 7XR5, the operation Baud-rate
must be 1200 BAUD.
2 4 0 0 B A U D
4 8 0 0 B A U D
9 6 0 0 B A U D
1 9 2 0 0 B A U D
7 0 0 3 D A T E F O R M A T
D D . M M . Y Y Y Y
The date inthe display is preset to the European format
Day.Month.Year. Switch-over to the American format
Month/Day/Year is achieved by depressing the
”No”---key N; then confirm with the entry key E.
DD two figures for the day
MM two figures for the month
YYYY four figures for the year (incl. century)
M M / D D / Y Y Y Y
7 0 0 4 F A U L T I N D I C
W I T H F A U L T D E T E C
Stored LED indications and the fault event messages in
the display can be displayed either with each fault de-
tection or only after trip command is given. This mode
can be changed by depressing the ”No”---key N and
confirmed with the enter---key E.
W I T H T R I P C O M M .