Installation instructions7SV512
V1
58
C53000---G1176---C91
5.5.3 Marshalling of the signal output relays --- address block 62
The unit contains 8 signal outputs (alarm relays).
The signal relays are designated SIGNAL RELAY 1
to SIGNAL RELAY 8 and can be marshalled in ad-
dress block 62. The block is reached by paging in
blocks withÝ ß orby directly addressing DA 6 2 0 0
E. The selection procedure is carried out as de-
scribed in Section 5.5.1. Multiple annunciations are
possible, i.e. one logical annunciation function can
be given to several physical signal relays (see also
Section 5.5.1).
Table 5.3 gives a listing of all annunciation functions
with the associated function numbers FNo. Annun-
ciation functions are naturally not effective when the
corresponding protection function is not fitted in the
relay or has been programmed out (de-configured
--- refer Section 5.4.2).
The assignment of the output signal relays as deliv-
ered from factory is shown in the general diagrams
in Appendix A. The following boxes show an ex-
ample formarshalling. Inthe example forsignalrelay
1 the group annunciation for several annunciation
functions on one signal relay is shown. Table 5.4
shows all signal relays as preset from the factory.
6 2 0 0 M A R S H A L L I N G
S I G N A L R E L A Y S
Beginning of the block Marshalling of the output
signal relays
The first signal relay is reached with the key ":
6 2 0 1 S I G N A L
R E L A Y 1
Allocations for signal relay 1
F
Change over to the selection level with F ":
0 0 1 R E L A Y 1
B F P - S t a r t
0 0 2 R E L A Y 1
P o l e D i s . S t a r t
Signal relay 1 has been preset for:
1st: Start of breaker failure protection, FNo 473;
Signal relay 1 has been preset for:
2nd: Start of pole discrepancy protection, FNo
601;
no further functions are preset for signal relay 1
0 0 3 R E L A Y 1
n o t a l l o c a t e d
Leave the selection level with key combination F ". You can go then to the next signal output relay with the
arrow key ".