Operating instructions7SV512
V1
91C53000---G1176---C91
6.4.4 Circuit breaker operation statistics --- address block 56
The number of trip commands initiated by 7SV512,
i.e. the number of breaker fail occurrences, is
counted. Additionally, the interrupted currents are
stated for each individual pole and given under the
fault annunciations (refer Section 6.4.3) following
each trip command. These currents are accumu-
lated and stored. Counter status and stores are se-
cured against auxiliary voltage failure and can be
read off under address 5600. The address can be
reached by direct addressing DA 5 6 0 0 E or by
paging with the keys Ý or ß until address 5600 is
reached. The counters can be called up using the
key " for forwards paging or # for backwards pag-
ing.
Entry of the codeword is not required for read-off of
counter states.
5 6 0 0 C B O P E R A T .
S T A T I S T I C S
Beginning of the block Circuit breaker operation
statistics
Number of circuit breaker failures, e.g. 1
Accumulated interrupted currents for CB pole L1
Accumulated interrupted currents for CB pole L2
Accumulated interrupted currents for CB pole L3
5 6 0 4 B / F N o =
1
Page on with key " to get further counter states
The maximum values of the counters are:
--- B/F No 9 digits
--- IL1/In, IL2/In, IL3/In 7 digits plus 1 decimal digit
5 6 0 7 I L 1 / I n =
5 6 0 8 I L 2 / I n =
5 6 0 9 I L 3 / I n =
The counters can be reset to 0 in block 82 (see Section 6.5.2).