Installation instructions7SV512
V1
56
C53000---G1176---C91
0 0 2 I N P U T 1
n o t a l l o c a t e d
0 0 1 I N P U T 1
> L E D r e s e t N O
Reset of stored LED indications, FNo 6;
”normally open” operation:
LEDs are reset when control voltage present
No further functions are initiated by binary input 1
Leave the selection level withkey combination F ".You can go then to the next binary input withthe arrowkey
".
6 1 0 1 B I N A R Y
I N P U T 1
Marshalling binary input 1
1 not allocated
5 >Time Synchro
6 >LED-reset
7 >Start FltRec
16 >CB Aux. L1
17 >CB Aux. L2
18 >CB Aux. L3
19 >CB Aux. 3p C
20 >CB Aux. 1p C
21 >Annunc. 1
22 >Annunc. 2
23 >Annunc. 3
24 >Annunc. 4
31 >B/F on
32 >B/F off
33 >Pole Dis. on
34 >Pole Dis.off
35 >Flt.Rec. on
36 >Flt.Rec. off
59 >ParamSelec.1
60 >ParamSelec.2
70 >Start
71 >Start N
72 >Trip
73 >Trip 3pole
74 >Trip L1
75 >Trip L2
76 >Trip L3
77 >B/F block
78 >CB defect
Binary input is not allocated to any input function
Synchronize internal real time clock
Reset LED indicators
Start fault recording from external command via binary input
Circuit breaker auxiliary contact L1 (L1 is closed)
Circuit breaker auxiliary contact L2 (L2 is closed)
Circuit breaker auxiliary contact L3 (L3 is closed)
Circuit breaker auxiliary contact all poles closed (series connection)
Circuit breaker auxiliary contact any pole closed (parallel connection)
User definable annunciation 1
User definable annunciation 2
User definable annunciation 3
User definable annunciation 4
Switch on breaker failure protection
Switch off breaker failure protection
Switch on pole discrepancy supervision
Switch off pole discrepancy supervision
Switch on fault recording function
Switch off fault recording function
Parameter set selection 1 (in connection with 060)
Parameter set selection 2 (in connection with 059)
General fault detection signal from feeder protection
Earth fault detection signal from feeder protection
General trip signal from feeder protection
Trip signal three-pole from feeder protection
Trip signal L1 from feeder protection
Trip signal L2 from feeder protection
Trip signal L3 from feeder protection
Block breaker failure protection
Circuit breaker defective from circuit breaker
FNo Abbreviation Description
Table 5.1 Marshalling possibilities for binary inputs