Installation instructions7SV512
V1
64
C53000---G1176---C91
0 0 2 T R I P R E L . 3
B F P T r i p L 1 2 3
Trip relay 3 has been preset for:
1st: Trip command for the local (feeder) circuit,
three-pole, FNo 505;
0 0 4 T R I P R E L . 3
n o t a l l o c a t e d
0 0 3 T R I P R E L . 3
P o l e D i s . T r i p
Trip relay 3 has been preset for:
3rd:Tripcommand frompole discrepancy supervi-
sion, FNo 610;
no further functions are preset for trip relay 1
Leave the selection level with key combination F ". You can go then to the next trip relay with the arrow key ".
6 4 0 3 T R I P
R E L A Y 3
Allocations for trip relay 3
6400
6401
6402
6403
6404
6405
TRIP RELAYS
RELAY 1
1
)
BFP Bus Trip
RELAY 2
1
)
BFP TransTrip
RELAY 2
BFP Trip L1
BFP Trip L123
PoleDis. Trip
RELAY 2
BFP Trip L2
BFP Trip L123
PoleDis. Trip
RELAY 2
BFP Trip L3
BFP Trip L123
PoleDis. Trip
507
508
502
505
610
503
505
610
506
505
610
MARSHALLING
TRIP
TRIP REL. 1
TRIP
TRIP REL. 2
TRIP
TRIP REL. 3
TRIP REL. 3
TRIP REL. 3
TRIP
TRIP REL. 4
TRIP REL. 4
TRIP REL. 4
TRIP
TRIP REL. 5
TRIP REL. 5
TRIP REL. 5
1st display lineAddr 2nd display line FNo
Remarks
Heading of the address block
Bus-bar trip command by breaker failure
protection
1
)
Transfer trip command by breaker failure
protection
1
)
Local trip commands for the individual
breaker poles (feeder breaker)
1
) Trip relays 1 and 2 should not be altered (see Attention above in this section).
Table 5.6 Preset command functions for trip relays