=USNJVOTPKV=G=fkpq^iiqflk=fkpqor`qflkp=Ua^=G=oÉîáëáçå=MP 41
fåëí~ää~íáçå
! Protect the connection socket of the voltage transformer against damages and
pollution.
! Close the outside-cone bushing at the panel with surge-proof covers.
Removing voltage transformer type 4MU1
! Push steel rods through the crane eyes of the retaining angle.
! Remove the fixing bolts of the retaining angles at the voltage transformer mounting
plate.
! Screw four press-out bolts into the holes provided for this purpose in the adapter
plate.
! Press the voltage transformer out of the bushing together with the retaining angles
with the help of the press-out bolts. While doing so, screw the press-out bolts in
uniformly, so that the transformer is not canted.
Fig. 27: Busbar voltage transformer 4MU1
a
Voltage transformer 4MU1
s
Retaining angle with crane eyes
d
Voltage transformer mounting
plate
f
Busbar housing
g
Distance sleeves
h
Outside-cone bushing
j
Hole with setnut for press-out
bolts
ATTENTION!
Risk of injury! While being removed from the bushing, the voltage transformer can
detach suddenly.
! Remove the voltage transformer upwards as uniformly as possible.
! Do not use excessive force.