42 oÉîáëáçå=MP=G=fkpq^iiqflk=fkpqor`qflkp=Ua^=G=USNJVOTPKV=
! Remove the voltage transformer upwards together with the retaining angles by
means of the steel rods.
! Protect the connection socket of the voltage transformer against damages and
pollution.
! Close the outside-cone bushing at the panel with surge-proof covers.
Removing voltage transformer type 4MT6
! Remove the fixing bolts at the voltage transformer base.
! Remove the fixing bolts of the retaining angle at the voltage transformer.
! Push steel rods through the crane eyes of the voltage transformer.
! Screw two press-out bolts into the holes provided for this purpose at the voltage
transformer base.
! Press the voltage transformer out of the bushing with the help of the press-out bolts.
While doing so, screw the press-out bolts in uniformly, so that the transformer is not
canted.
ATTENTION!
Risk of injury! The voltage transformer type 4MU1 has a weight of approx. 50 kg.
! Secure the voltage transformer against falling down.
! If necessary, transport the voltage transformer with several persons or with suitable
aids.
Fig. 28: Busbar voltage transformer 4MT6
a
Crane eyes
s
Voltage transformer 4MT6
d
Retaining angle
f
Busbar housing
g
Inside-cone bushing
h
Adapter ring
j
Voltage transformer base
k
Hole for press-out bolts