EasyManua.ls Logo

Siemens 8DA - Page 44

Siemens 8DA
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
fåëí~ää~íáçå
44 oÉîáëáçå=MP=G=fkpq^iiqflk=fkpqor`qflkp=Ua^=G=USNJVOTPKV=
Preparing installation for
4MT3 and 4MU1
! Isolate and earth the busbar.
! Verify safe isolation from supply.
! Apply a uniform film of mounting paste to the silicone bushing of the voltage
transformer.
! Insert the silicone bushing in the voltage transformer.
! Remove surge-proof caps from the outside-cone bushings.
! Earth the connecting lug of the capacitive layer of the outside-cone bushing.
! Apply a uniform film of mounting paste to the outside-cone bushing.
! Voltage transformer type 4MT3: If not yet pre-assembled, mount the adapter plate
on the voltage transformer.
ATTENTION!
Risk of partial discharges at the voltage transformer bushings due to pollution.
! Clean all bushings at the panel and at the voltage transformer carefully before
starting installation work.
! Observe extreme cleanliness while working.
ATTENTION!
Risk of partial discharges at the outside-cone bushing.
! Make sure that the connecting lug of the capacitive connecting point of the outside-
cone bushing is earthed.

Table of Contents

Other manuals for Siemens 8DA