500-8067.9 * INSTALLATION AND OPERATING INSTRUCTIONS 8DJH * Revision 03 53
Description
Transformer protection table:
Recommendation for the allocation of HV HRC fuse-links make SIBA and transformers
Transformer HV HRC fuse
U [kV] S
N
[kVA] u
K
[%] I
1
[A] I
s
[A] U
s
[kV] e [mm] Order no.
3.3-3.6 20 4 3.5 6.3 3-7.2 292 30 098 13.6,3
10 3-7.2 292 30 098 13.10
30 4 5.25 10 3-7.2 292 30 098 13.10
16 3-7.2 292 30 098 13.16
50 4 8.75 16 3-7.2 292 30 098 13.16
20 3-7.2 292 30 098 13.20
75 4 13.1 20 3-7.2 292 30 098 13.20
25 3-7.2 292 30 098 13.25
100 4 17.5 31.5 3-7.2 292 30 098 13.31,5
40 3-7.2 292 30 098 13.40
125 4 21.87 31.5 3-7.2 292 30 098 13.31,5
40 3-7.2 292 30 098 13.40
160 4 28 40 3-7.2 292 30 098 13.40
50 3-7.2 292 30 098 13.50
200 4 35 50 3-7.2 292 30 098 13.50
63 3-7.2 292 30 099 13.63
250 4 43.74 63 3-7.2 292 30 099 13.63
80 3-7.2 292 30 099 13.80
4.16-4.8 20 4 2.78 6.3 3-7.2 292 30 098 13.6,3
30 4 4.16 10 3-7.2 292 30 098 13.10
50 4 6.93 16 3-7.2 292 30 098 13.16
75 4 10.4 16 3-7.2 292 30 098 13.16
20 3-7.2 292 30 098 13.20
100 4 13.87 20 3-7.2 292 30 098 13.20
25 3-7.2 292 30 098 13.25
125 4 17.35 25 3-7.2 292 30 098 13.25
31.5 3-7.2 292 30 098 13.31,5
160 4 22.2 31.5 3-7.2 292 30 098 13.31,5
40 3-7.2 292 30 098 13.40
200 4 27.75 40 3-7.2 292 30 098 13.40
50 3-7.2 292 30 098 13.50
250 4 34.7 50 3-7.2 292 30 098 13.50
63 3-7.2 292 30 099 13.63
315 4 43.7 63 3-7.2 292 30 099 13.63
80 3-7.2 292 30 099 13.80
5.0-5.5 20 4 2.3 6.3 3-7.2 292 30 098 13.6,3
30 4 3.4 6.3 3-7.2 292 30 098 13.6,3
10 3-7.2 292 30 098 13.10
50 4 5.7 10 3-7.2 292 30 098 13.10
16 3-7.2 292 30 098 13.16
75 4 8.6 16 3-7.2 292 30 098 13.16
20 3-7.2 292 30 098 13.20
100 4 11.5 16 3-7.2 292 30 098 13.16
20 3-7.2 292 30 098 13.20
125 4 14.4 20 3-7.2 292 30 098 13.20
25 3-7.2 292 30 098 13.25