500-8067.9 * INSTALLATION AND OPERATING INSTRUCTIONS 8DJH * Revision 03 85
Installation
Ö If necessary, detach the cross members j to swing in the cables.
Ö Pre-adjust the cable bracket g and the lower part of the cable clamps h.
Ö If available, mount cable-type current transformers (see Page 93, "Cable connection
with cable-type current transformers".
Ö Fit the plugs on the conductor ends according to the manufacturers instructions.
Ö Carefully coat the push-on surfaces (high-quality joints) in the plug sets and the
bushing cone with mounting paste (scope of supply of the plug set).
Ö Push the plug sets a to d onto the bushing and fix them according to the
manufacturers instructions. Observe the phase sequence!
Ö Mount the upper part of the cable clamps h, align the cable bracket and bolt it tight.
Ö Connect the cable shield and the earthing of the plug housing at the front cross
member j.
Double cables and surge arresters can be connected to ring-main feeders using
adequate plug-in cable systems.
Please observe the following:
Depending on their type, double cable connections require a deep cable compartment
cover and larger floor openings.
Depending on their type, surge arresters also require a deep cable compartment cover.
For details, please refer to the order documents.