Chapter 4 - Parameters and Menu Structure
Defines the drive data to supervise for
Superv2 Mode (P3.8.6) in accordance
with the Superv2 Limit (P3.8.7) with
deadband defined with Superv2 Hyst
(P3.8.8)
Refer to
Superv1 Item
(P3.8.1) for
settings.
NOTE:
A relay output can be triggered
in accordance with this supervised item.
Set Relay Output Function to a value of
Superv2 Lmt.
Defines the type of supervision of the
Superv2 Item (P3.8.5) in accordance
with the Superv2 Limit (P3.8.7) with
deadband defined with Superv2 Hyst
(P3.8.8)
0 = Not used
1 = Low Limit Supervision
2 = High Limit Supervision
Defines the limit that Superv2 Item
(P2.8.5) is compared to, which
determines if Superv2 Mode (P3.8.6)
has occurred. Unit of measure appears
automatically.
Defines the deadband of Superv1 Item
(P3.8.5).
Example:
To energize relay output 1 when the motor output current has reached 4 amps and have the drive act like a current
transducer (CT). Complete the following:
1. Set Supervision Item 1 Selection (P3.8.1) to a value of Motor Current.
2. Set Supervision Item 1 Mode (P3.8.2) to a value of High Limit.
3. Set Supervision Item 1 Limit (P3.8.3) to a value of 4.
4. Set RO1 Function (P3.5.3.2.1) to a value of LimSuperv1.