Chapter 4 - Parameters and Menu Structure
Protections (M3.9)
Protections define the way the drive is to respond to conditions that can occur in the drive.
Table 46: Protections Settings.
Defines the response to a low analog input
signal. Response settings are as follows:
0 = No Action
1 = Alarm
2 = Alarm and run to PresetAlarmFreq
(P3.3.19)
3 = Fault
(stop according to stop mode)
4 = Fault
(stop by coasting)
Defines the response to activation of an
Ext Fault Close (P3.5.1.7) or Ext Fault
Open (P3.5.1.8). Response settings are as
follows:
0 = No Action
1 = Alarm
2 = Fault
(stop according to stop mode)
3 = Fault
(stop by coasting)
Defines the input phase support.
0 = 3-phase support
1 = 1-phase support
NOTE
: If single phase supply is used, 1-
phase support must be selected.
Defines if the under-voltage fault is stored
in the fault history or not.
0 = Fault Stored
1 = No History
Defines the response to an output phase
loss. Response settings are as follows:
0 = No Action
1 = Alarm
2 = Fault
(stop according to stop mode)
3 = Fault
(stop by coasting)
Defines the response to a motor thermal
protection. Response settings are as
follows:
0 = No Action
1 = Alarm
2 = Fault
(stop according to stop mode)
3 = Fault
(stop by coasting)
Defines the ambient temperature that is to
generate a response to a Motor Thermal
Protection fault as defined by Motor Therm
Prot (P3.9.6.
Defines the cooling factor at zero speed in
relation to the point where the motor is
running at nominal speed without external
cooling.
The time constant is the time within which
the calculated thermal stage has reached
63% of its final value.
Motor thermal loadability states how much
the motor can be thermally loaded.