Chapter 4 - Parameters and Menu Structure
Defines the response to a motor stall.
Response settings are as follows:
0 = No Action
1 = Alarm
2 = Fault
(stop according to stop mode)
3 = Fault
(stop by coasting)
For a stall stage to occur, the current must
have exceeded this limit.
This is the maximum time allowed for a
stall stage.
For a stall stage to occur, the output
frequency must have remained below this
limit for a certain time.
Defines the response to an underload.
Response settings are as follows:
0 = No Action
1 = Alarm
2 = Fault
(stop according to stop mode)
3 = Fault
(stop by coasting)
This parameter gives the value for the min
torque allowed when the output frequency
is above the field weakening point.
This parameter gives the value for the min
torque allowed with zero frequency.
This is the maximum time allowed for an
underload state to exist.
Defines the response to a fieldbus
communications signal loss. Response
settings are as follows:
0 = No Action
1 = Alarm
2 = Alarm and run to PresetAlarmFreq
(P3.3.19)
3 = Fault
(stop according to stop mode)
4 = Fault
(stop by coasting)
Defines the response to an option card slot
communications failure. Response settings
are as follows:
0 = No Action
1 = Alarm
2 = Fault
(stop according to stop mode)
3 = Fault
(stop by coasting)
Defines the response to a thermistor
failure. Response settings are as follows:
0 = No Action
1 = Alarm
2 = Fault
(stop according to stop mode)
3 = Fault
(stop by coasting)
NOTE
: It is recommend to set to a value of
Fault (according to stop mode) if a BT300-
OPT-B4-V option card is installed.