When only one value is selectable:
Stage 1
The checked off line (Fire Setpoint) displays the presently set value. Change the 
value as follows:
●● Select new value: Turn the navigation dial.
●● Assume new value and exit the setting page: Press the navigation dial.
or
●● Retain old value and exit the setting page: Press the ESC button.
When multiple values can be selected:
enblOffNormal
enb lFault
selfRelea se
type Alarm
Checked off lines display presently selected values. Change values as follows:
●● Select new value: Turn the navigation dial.
●● Select or deselect value: Press the navigation dial.
●● Assume the new value: 
–  Select Done: Turn the navigation dial.
–  Select Done: Press the navigation dial.
or
●● Retain the old value and exit the setting page: Press the ESC button.
The scale displays minimum and maximum adjustable values. 
Change the preset value as follows:
●● Adjust the number under the arrow  : Turn the navigation dial.
●● To move the arrow to the left: Turn continuously via increments of ten  
(9--->0 or 0--->9).
●● To move the arrow to the right: Do not turn the knob for at least one second.
●● Assume the new value and exit the setting page: Press the navigation dial.
or
●● Retain the old value and exit the setting page: Press the ESC button.
To set discrete parameter 
values..
Short Manual for Climatix Control System [v. 2.14.10, 2.14.20, 2.14.30 & 2.14.40]