9 Compatibility with Predecessor Products
B4A56
CP 443-1 Advanced for Industrial Ethernet / Manual Part B4A
Release 01/2007
C79000-G8976-C193-06
9.2 Restrictions
Compared with previous modules, please note the following general restrictions:
S Existing project engineering data is not accepted without replacing the
previously used module type with the new module type in STEP 7 / HW Config;
S Removing / inserting the CP when the power supply is turned on causes an I/O
error on the CPU; this I/O error can only be cleared by turning the power supply
for the rack off and on again.
S The configuration data is stored only on the CPU (module replacement possible
without PG);
S Downloading the firmware requires the mode selector to be set to ”STOP” and
the power supply must be turned off and on.
S The 15pin Dsub connector for connecting AUI or Ind. Twisted Pair has been
omitted.
S The CP is not intended for operation with an S7400H programmable controller
(faulttolerant system).