10 Further Notes on Operation
B4A61
CP 443-1 Advanced for Industrial Ethernet / Manual Part B4A
Release 01/2007
C79000-G8976-C193-06
Resetting to Factory Settings Effects
After it has been reset to the factory settings, the CP still has the MAC address
that was set in the factory (as shipped).
The data in the file system of the C-PLUG (flash area) is retained, the retentive
parameters are deleted.
Overall, this has the following effects:
Data maintained on the S7-400
CPU.
Deleted data areas
Factory-set MAC
address
Fixed data
CPLUG
Retentive parameters
Flash file system
RAM Area
Volatile RAM file
system (/ram)
Non-volatile RAM file
system (/sram)
Battery backed
RAM area
CPU data
Configuration Data
Note
Please note that the interconnection information for PROFINET CBA belongs to
the retentive parameters in the CPLUG and will therefore be deleted when you
reset to the factory settings.