10 Further Notes on Operation
B4A70
CP 443-1 Advanced for Industrial Ethernet / Manual Part B4A
Release 01/2007
C79000-G8976-C193-06
Supported MIB Objects
The CP supports all MIB objects of the standard MIB according to MIB II (RFC
1213).
Exceptions / Restrictions:
S Write access is permitted only for the following MIB objects:
sysContact, sysLocation and sysName;
For security reasons, only read access is permitted for all other MIB objects.
S Traps are not supported by the CP.
MIB Object “Interfaces”
The “Interfaces” MIB object provides status information on the CP interfaces, with
the following assignment:
Index ifDescr
14 Port 14
5 Internal CP interface
Access Permissions using Community Name
The CP uses the following community names for assigning permissions:
S For read access: “public”
S for read and write access: “private”
(note the use of lowercase letters!)

Table of Contents