Article number 6ES7512-1DM03-0AB0
–
Number of connections, max. 4
–
Number of nodes of the client inter
faces, max.
1000
–
Number of elements for one call of
OPC_UA_NodeGetHandleList/OPC_UA_
ReadList/OPC_UA_WriteList, max.
300
–
Number of elements for one call of
OPC_UA_NameSpaceGetIndexList,
max.
20
–
Number of elements for one call of
OPC_UA_MethodGetHandleList, max.
100
–
Number of simultaneous calls of the
client instructions per connection
(except
OPC_UA_ReadList,OPC_UA_WriteList,
OPC_UA_MethodCall), max.
1
–
Number of simultaneous calls of the
client instructions
OPC_UA_ReadList,OPC_UA_WriteList
and OPC_UA_MethodCall, max.
5
–
Number of registerable nodes, max. 5000
–
Number of registerable method calls of
OPC_UA_MethodCall, max.
100
–
Number of inputs/outputs when calling
OPC_UA_MethodCall, max.
20
•
OPC UA Server Yes; Data Access (Read, Write, Subscribe), Meth
od Call, Alarms & Condition (A&C), Custom
Address Space
–
Application authentication Yes
–
Security policies available security policies: None, Basic128Rsa15,
Basic256Rsa15, Basic256Sha256,
Aes128Sha256RsaOaep, Aes256Sha256RsaPss
–
User authentication "anonymous" or by user name & password
–
GDS support (certificate management) Yes
–
Number of sessions, max. 32
–
Number of accessible variables, max. 50000
–
Number of registerable nodes, max. 10000
–
Number of subscriptions per session,
max.
50
–
Sampling interval, min. 100ms
–
Publishing interval, min. 200ms
–
Number of server methods, max. 20
–
Number of inputs/outputs per server
method, max.
20
–
Number of monitored items, max. 4000; for 1 s sampling interval and 1 s send
interval