4 Configuration and Project Engineering
4.3 Safe Torque Off (STO)
with Safety Integrated
SINAMICS G120 as a Speed Axis on the S7-1500
V1.0a, Entry ID: 78788716
31
Copyright Siemens AG 2013 All rights reserved
No. Action Picture
1. Enter the current password.
Change the default password
“0” of a factory new
SINAMICS G120.
Note:
When resetting the safety
parameters to factory
settings, the assigned
password remains.
2. Select the safety functionality.
1. Make sure that the safety
commissioning is
activated.
2. Navigate to the selection
of the safety functionality.
3. Select the “Basic
functions”.
4. Click on the “Control type
/ safety functions” button.
3. Select control type and safety
function.
1. Select the control type
“via terminals” (default
setting).
2. Click on the “STO” safety
function (the only one
available).
4. Output “STO active”
On demand you can
interconnect the “STO active”
output. However, this is not
necessary in this application.
1
2
3
4
1
2

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals