Converter with Control Units CU230P-2; CU240B-2; CU240E-2
Getting Started, 11/2013, A5E32885834B AA
23
Installing
3
3.1
Installing the Power Module
WARNING
Danger of death caused by high leakage currents when the external protective conductor is
interrupted
The inverter conducts high leakage currents > 3.5 mA via the protective conductor. When
the protective conductor is interrupted, touching live components can result in electric
shock, which can lead to death or serious injuries.
Connect a protective conductor, which satisfies at least one of the following conditions,
to the inverter:
The protective conductor is routed so that it is protected against mechanical damage.
Cables routed in control cabinets or enclosed machine enclosures are considered to
be adequately protected.
The protective conductor routed as an individual conductor has a cross-section of
10 mm² Cu.
In a multi-core cable the protective conductor has a cross-section of ≥ 2.5 mm² Cu.
Two parallel protective conductors with the same cross-section are installed.
The protective conductor corresponds to the local regulations for equipment with
increased leakage current.
Connecting the Power Module to the motor and power supply
Figure 3-1 Connecting the PM340 1AC Power Module

Other manuals for Siemens CU240B-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CU240B-2 and is the answer not in the manual?

Siemens CU240B-2 Specifications

General IconGeneral
BrandSiemens
ModelCU240B-2
CategoryInverter
LanguageEnglish

Related product manuals