5.4 Resetting extended alarms
Extended alarms additionally require a reset. Delete the
associated pop-up window by pressing Esc.
The alarm can only be reset after the fault has been cleared.
Step Procedure
1 Navigate to the Alarms option (Figure 5-4)
2
Confirm with OK. The alarm list opens (Figure 5-3)
3
Highlight the required alarm and confirm with OK.
4
Clear the fault
5
Open the alarm list again
6
Select the required alarm and confirm with OK.
Figure 5-8 Resetting an alarm
7 Use the push-dial to select No or Yes
8
Confirm with OK to reset the alarm.
9
The alarm disappears from the alarm list.