EWA 4NEB 780 6024-02 07
Table 6-2 Configuration Table and Address Space
Slot
Module Grouping I/O Address
Inputs Outputs
1 6ES7 138-4CA00-0AA0 PM-E 24 VDC ––– ––– –––
2 6ES7 131-4BB00-0AB0 2DI 24 VDC Yes 0.0 to 0.1
3 6ES7 131-4BB00-0AB0*2DI 24 VDC 0.2 to 0.3
4 6ES7 134-4FB00-0AB0 2AI U No 1 to 4
5 6ES7 135-4GB00-0AB0 2AO I No 0 to 3
6 6ES7 131-4BD00-0AA0*4DI 24 VDC Yes 0.4 to 0.7
7 6ES7 132-4BD00-0AA0 4DO 24 VDC Yes 4.0 to 4.3
8 6ES7 132-4BB00-0AB0*2DO 24 VDC 4.4 to 4.5
9 6ES7 132-4HB00-0AB0*2DO Rel. 4.6 to 4.7
10 6ES7 134-4FB00-0AB0 2AI U No 5 to 8
11 6ES7 135-4GB00-0AB0 2AO I No 5 to 8
12 6ES7 138-4CA00-0AA0 PM-E 24 VDC ––– ––– –––
13 6ES7 132-4BB30-0AB0 2DO 24 VDC Yes 9.0 to 9.1
14 6ES7 132-4BB30-0AB0* 2DO 24 VDC Yes 9.2 to 9.3
15 6ES7 138-4CA00-0AA0 PM-E AC230 ––– ––– –––
16 6ES7 132-4FB00-0AB0* 2DO 230 V Yes 9.4 to 9.5
17 6ES7 132-4FB00-0AB0* 2DO 230 V Yes 9.6 to 9.7
18 3RK1903-0BA00 PM-D ––– ––– –––
19 3RK1301-xxB00-0AA0 DS Yes 9.0 to 9.3 10.0 to 10.3
20 3RK1301-xxB00-0AA0 *DS 9.4 to 9.7 10.4 to 10.7
21 3RK1301-xxB00-0AA0 DS Yes 10.0 to 10.3 11.0 to 11.3
No Grouping
If you do not want to group the configuration of the ET 200S distributed I/O system
digital input/output modules and motor starters in a single byte, use only those
module designations without * in the hardware catalog of your configuration
software.
Each electronic module/motor starter will then occupy one byte in the input or
output area of the process image.