Configuration Options
3-27
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Procedure for Parameterizing Clocking
1. Carry out settings on the CPU:
Object Properties of the CPU > Clocked Interrupts tab
Set the CPU clocked interrupt
Select the DP master system used.
Select the desired partial process image.
Memory Interrupts Time-of-day interrupts Cyclic interrupts Diagnostics / clock
General Startup Clocked interrupts Cycle / clock memory Retentivity
OB 61:
Priority
DP master
system no.
Process image parti-
tion(s) (e.g.: 1.4)
Time lag
1 1 ms
Default
0.000
25
25
Figure 3-6 Clocked Interrupts Dialog Box
2. Carry out settings on the DP master system:
Object Properties of the DP master > General tab > Properties button >
Parameters tab > Properties button > Network Settings tab > Options
button
Activate equidistance on the DP master system
Set the length of the equidistant DP cycle (max. 250 ms).
Set Times Ti and To same for all Slaves (results in synchronization of the
I/O data of the different DP slaves)
You can set the Ti and To times separately. Recommended: Accept the
default settings for Ti and To.