Commissioning and Diagnostics
6-33
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
6.6.4 Master PROFIBUS Address
Definition
The master PROFIBUS address diagnostic byte contains the PROFIBUS address
of the DP master that:
Assigned parameters to the DP slave and
Has read and write access to the DP slave
The master PROFIBUS address is in byte 3 of the slave diagnosis.
6.6.5 Manufacturer ID
Definition
The manufacturer ID contains a code that describes the type of the DP slave.
Manufacturer ID
Table 6-11 Structure of the Manufacturer ID (Bytes 4, 5)
Byte 4 Byte 5 Manufacturer ID for
80
H
F3
H
ET 200S with IM151-1 BASIC
80
H
6A
H
ET 200S with IM151-1 STANDARD
80
H
6B
H
ET 200S with IM151-1 FO STANDARD
80
H
E0
H
ET 200S with IM151-1 HIGH FEATURE